Product Highlights
Topology
True online double-conversion
Phase Configuration
Single Phase Input / Single Phase Output
Available Capacities
6 kVA and 10 kVA
Form Factors
Tower and Rack/Tower Convertible
Online Efficiency
Up to 95%
ECO Mode Efficiency
Up to 98%
Input Power Factor
Up to 0.99
Output Power Factor - Tower
0.9
Output Power Factor - Rack/Tower
1.0
Control
Advanced dual-core DSP
Battery Flexibility
Internal and external battery support
Standard Features
Technology
High frequency online double conversion
Control
Advanced dual-core DSP and 3-level technology
APFC
Input power factor up to 0.99
Dual Input
Supports independent bypass
Parallel Operation
Up to 4 units
Input Frequency
50 / 60 Hz auto-sensing
Frequency Conversion
50 Hz / 60 Hz mode
Battery Management
Equalized and float charging with charger dormancy control
Battery Quantity
30 to 44 batteries selectable
Digital Charger
Maximum 48 A
Fan Control
Intelligent variable fan speed
Fault Tolerance
One fan failure supports 50% load; two fan failures support 30%
Harsh Environment
Conformal coating
Diagnostics
Hardware/software protection, self-diagnosis and event logs
Cold Start
Start from battery without mains
Delayed Start
Settable after mains restoration
Display
5" color LCD touch screen
Compliance
Standard 1
EN/IEC 62040-1 (LVD)
Standard 2
EN/IEC 62040-2 (EMC)
Standard 3
EN/IEC 62040-3
Construction & Finish
Power Architecture
3-level IGBT based
Control
DSP dual-core microprocessor controlled
Battery Connection
Internal / external battery through high-current charger
Surface Preparation
Degreasing salinization
Finish
Electrostatic spray
Ordering Information
6KT11NB16E
Fluence SentryUPS 11 Series 6kVA Tower UPS Single Phase
10KT11NB16E
Fluence SentryUPS 11 Series 10kVA Tower UPS Single Phase
6KRT11NB16E
Fluence SentryUPS 11 Series 6kVA Rack/Tower Convertible UPS Single Phase
10KRT11NB16E
Fluence SentryUPS 11 Series 10kVA Rack/Tower Convertible UPS Single Phase
COMSNTSNMP
Fluence UPS SNMP Network Card for SentryUPS Series
COMSNTRS485
Fluence UPS RS-485 Network Card for SentryUPS Series
Input Specifications
Input Wiring
Single Phase 3-wire (1Φ + N + PE)
Rated Voltage
220 / 230 / 240 Vac
Voltage Range
90–176 Vac with linear derating; 176–288 Vac without derating
Rated Frequency
50 / 60 Hz auto-sensing
Frequency Range
40 Hz @ 110V to 70 Hz @ 230V
Bypass Voltage Range
-40% to +15%, settable
Output Specifications
Output Wiring
Single-phase 3-wire (1Φ + N + PE)
Rated Voltage
220 / 230 / 240 Vac
Frequency
Synchronized with utility; 50 / 60 Hz ±0.1% in battery mode
Power Factor - Rack/Tower
1.0
THDv
≤1% linear load; ≤4% non-linear load
Overload
105–110% for 10 min; 110–125% for 1 min; 126–150% for 30 s
Battery System
DC Voltage
192 Vdc, adjustable 192–240 Vdc
Default Battery Quantity
16 pcs
Settable Battery Quantity
16–20 pcs
Battery Derating Range
18–15 pcs with linear derating to 50%
Recharge Time - Standard Model
90% capacity restored in 8 hours
Recharge Time - Long Time Model
Depends on battery capacity
System & Communication
Protections
Short-circuit, overload, over-temperature, battery low voltage, overvoltage, undervoltage, fan failure
Maximum Parallel Connections
4
Standard Communication
RS232
Optional Communication
SNMP, USB, RS485, RJ45, dry contacts, Wi-Fi, GPRS
Environmental
Operating Temperature
0°C to 40°C
Storage Temperature
-25°C to 55°C without battery
Relative Humidity
0–95% non-condensing
Altitude
≤1000 m; derating 1% per additional 100 m
Noise Level
≤58 dB at 1 m
Model Dimensions & Weights
6KT11NB16E
6 kVA / 6 kW Tower — 191×500×515 mm — Net 14.5 kg — Gross 16 kg
10KT11NB16E
10 kVA / 10 kW Tower — 191×500×515 mm — Net 15.5 kg — Gross 17 kg
6KRT11NB16E
6 kVA / 6 kW Rack/Tower — 440×660×176 mm — Net 12 kg — Gross 14 kg
10KRT11NB16E
10 kVA / 10 kW Rack/Tower — 440×660×176 mm — Net 14 kg — Gross 16 kg