Product Highlights
Topology
True online double-conversion
Phase Configuration
3-Phase Input / 3-Phase Output
Frame Capacities
160 kVA and 200 kVA
Custom Solutions
Up to 1.2 MVA available on demand
Power Modules
20 kVA and 25 kVA
Online Efficiency
Up to 96%
ECO Mode Efficiency
Up to 99%
Input Power Factor
Up to 0.99
Modular Design
Hot-swappable power, bypass and control modules
Bypass
Built-in modular bypass switch and integrated maintenance bypass panel
Display
7" LCD touch screen
Standard Features
Technology
High frequency online double conversion
Control
Advanced dual-core DSP and 3-level technology
Active PFC
Input power factor up to 0.99
Dual Input
Supports independent bypass
Parallel Technology
Advanced digital and parallel technology
Input Frequency
50 / 60 Hz auto-sensing
Frequency Conversion
50 Hz / 60 Hz mode
Battery Management
SOC, SOH, equalized and float charging, charger hibernation
Battery Quantity
30 to 46 batteries selectable
Hot Swap
Power, bypass and control modules support plug & play
Communication
SNMP, RS485 and Dry Contacts
Harsh Environment
Conformal coating technology
Diagnostics
Self-diagnosis and event logging
Cold Start
UPS can start from battery without mains
Delayed Start
Settable delayed start after mains restoration
Compliance
Standard 1
EN/IEC 62040-1 (LVD)
Standard 2
EN/IEC 62040-2 (EMC)
Standard 3
EN/IEC 62040-3
Construction & Finish
Power Architecture
3-level IGBT based
Control
DSP dual-core microprocessor controlled
External Battery Connection
High-current charger connection
Surface Preparation
Degreasing salinization
Finish
Electrostatic spray
Ordering Information
160(20)MD33HC30-46
Fluence FlexUPS Modular Series Frame 160kVA UPS 3P/3P (20kVA modules only)
200(25)MD33HC30-46
Fluence FlexUPS Modular Series Frame 200kVA UPS 3P/3P (25kVA modules only)
PM(20)MD33
Fluence FlexUPS Modular Series Power Module 20kVA
PM(25)MD33
Fluence FlexUPS Modular Series Power Module 25kVA
Input Specifications
Input Wiring
Three-phase five-wire (3Φ + N + PE)
Rated Voltage
380 / 400 / 415 Vac
Voltage Range
304–485 Vac without derating; 138–304 Vac with linear derating
Rated Frequency
50 / 60 Hz auto-sensing
Bypass Voltage Range
-60% to +20%, settable
Output Specifications
Output Wiring
Three-phase five-wire (3Φ + N + PE)
Rated Voltage
380 / 400 / 415 Vac
Frequency
Synchronized with utility; 50 / 60 Hz ±0.1% in battery mode
THDv
≤1% linear load; ≤4% non-linear load
Overload
105–110% for 60 min; 110–125% for 10 min; 125–150% for 1 min; >150% for 0.2 s
Battery System
DC Voltage
±240 Vdc, adjustable ±180 to ±276 Vdc
Number of Batteries
32 pcs standard, 30–46 pcs settable
Charging Current
Adaptive with ABM
Recharge Time
0–80% within 2 hours; 80–100% within 8 hours
System & Communication
Online Efficiency
Max. 96%
Protections
Short-circuit, overload, over-temperature, battery low voltage, undervoltage, overvoltage, fan failure
Standard Communication
RS485, CAN, NET, SNMP, dry contacts port, EPO
Optional Communication
Wi-Fi card, parallel port, LBS port, 4G card, battery temperature sensor, EMD
Display
7" LCD touch screen
Environmental
Operating Temperature
0°C to 40°C
Storage Temperature
-25°C to +55°C without battery
Relative Humidity
0–95% non-condensing
Altitude
≤1000 m; derating 1% per additional 100 m
Model Dimensions
160(20)MD33HC30-46
160 kVA / 160 kW — Cabinet 600×850×1800 mm — Net weight 250 kg — Module 20 kVA / 20 kW
200(25)MD33HC30-46
200 kVA / 200 kW — Cabinet 600×850×2000 mm — Net weight 280 kg — Module 25 kVA / 25 kW
20 kVA Power Module
442×620×86 mm — 21 kg
25 kVA Power Module
442×620×86 mm — 23 kg